An office building was experiencing loud toilet flushing noise in offices adjacent to the toilets. The toilets were a 1.2 gallon per flush model. A study by others documented some maximum A‐weighted slow sound levels greater than 60 dB with most greater than 50 dB and recommended a limit of 40 dB. The building owner made changes including an improved wall on one of the seven affected floors and asked the author to repeat the measurements. Results were mostly in the range of 40 to 50. Sound levels within the rest rooms were greater than 80 dB, and within the toilet stall of the loudest toilet—96 dB. The sound peaked in the 2000 Hz octave. A wall on one floor was modified by adding a layer of damped gypsum with successful results. The remaining walls were then modified similarly. The resulting average level of four flushes was less than 40 dB in all offices though some individual flushes were slightly greater than 40 dB. It was evident that structural flanking was controlling the remaining sound reaching the offices.
Skip Nav Destination
Article navigation
April 2011
Meeting abstract. No PDF available.
April 01 2011
An experience reducing toilet flushing noise reaching adjacent offices. Free
Noral D. Stewart
Noral D. Stewart
Stewart Acoust. Consultants, 7330 Chapel Hill Rd., Ste. 101, Raleigh, NC 27607, [email protected]
Search for other works by this author on:
Noral D. Stewart
Stewart Acoust. Consultants, 7330 Chapel Hill Rd., Ste. 101, Raleigh, NC 27607, [email protected]
J. Acoust. Soc. Am. 129, 2605 (2011)
Citation
Noral D. Stewart; An experience reducing toilet flushing noise reaching adjacent offices.. J. Acoust. Soc. Am. 1 April 2011; 129 (4_Supplement): 2605. https://doi.org/10.1121/1.3588639
Download citation file:
619
Views
Citing articles via
Focality of sound source placement by higher (ninth) order ambisonics and perceptual effects of spectral reproduction errors
Nima Zargarnezhad, Bruno Mesquita, et al.
A survey of sound source localization with deep learning methods
Pierre-Amaury Grumiaux, Srđan Kitić, et al.
Drawer-like tunable ventilated sound barrier
Yong Ge, Yi-jun Guan, et al.
Related Content
Soundscape of washroom equipment and its application
J. Acoust. Soc. Am. (May 2017)
Design of cost-effective grey water management unit for diverse hydraulic and organic loadings using green technologies
AIP Conf. Proc. (March 2025)
Acoustical privacy for closed office design
J. Acoust. Soc. Am. (August 2005)
A case history of office building plumbing noise, its causes and reduction.
J. Acoust. Soc. Am. (April 2011)
Two case histories relating to the transmission of noise from mechanical equipment rooms to adjacent noise sensitive spaces
J. Acoust. Soc. Am. (November 2013)