The purpose of this paper is to examine energy efficiency through the study of performance in vapour compression cycle for auditorium in University of Indonesia using natural refrigerant R290. The installation of the chiller system which is the first in Indonesia within academic institution is particularly relevant in light of the gaining interest and research regarding the implementation of refrigeration system utilizing relatively low ODP and GWP refrigerant as alternative to replace the refrigerant HCFC-22. It is found that the highest COP during 64% partial cooling load is 4.27 at temperature water inlet is 8.9°C. The maximum COP during 75% partial load is 5.25 at temperature water inlet is 6,8 °C. The cooling capacity are 125.93 kW and 148.39 kW during 64% and 75% load, respectively.
Skip Nav Destination
Article navigation
25 January 2019
THE 10TH INTERNATIONAL MEETING OF ADVANCES IN THERMOFLUIDS (IMAT 2018): Smart City: Advances in Thermofluid Technology in Tropical Urban Development
16–17 November 2018
Bali, Indonesia
Research Article|
January 25 2019
Chiller performance study with refrigerant R290
Zulfa Fuadi;
Zulfa Fuadi
a)
Department of Mechanical Engineering, Faculty of Engineering, Universitas Indonesia
, Kampus UI Depok 16424, Indonesia
Search for other works by this author on:
Ardiyansyah Yatim;
Ardiyansyah Yatim
b)
Department of Mechanical Engineering, Faculty of Engineering, Universitas Indonesia
, Kampus UI Depok 16424, Indonesia
b)Corresponding author: ardiyansyah@eng.ui.ac.id
Search for other works by this author on:
Rachmah Rizky;
Rachmah Rizky
c)
Department of Mechanical Engineering, Faculty of Engineering, Universitas Indonesia
, Kampus UI Depok 16424, Indonesia
Search for other works by this author on:
Nyayu Aisyah;
Nyayu Aisyah
d)
Department of Mechanical Engineering, Faculty of Engineering, Universitas Indonesia
, Kampus UI Depok 16424, Indonesia
Search for other works by this author on:
Idrus Alhamid;
Idrus Alhamid
e)
Department of Mechanical Engineering, Faculty of Engineering, Universitas Indonesia
, Kampus UI Depok 16424, Indonesia
Search for other works by this author on:
Budihardjo Budihardjo;
Budihardjo Budihardjo
f)
Department of Mechanical Engineering, Faculty of Engineering, Universitas Indonesia
, Kampus UI Depok 16424, Indonesia
Search for other works by this author on:
Nandy Putra
Nandy Putra
g)
Department of Mechanical Engineering, Faculty of Engineering, Universitas Indonesia
, Kampus UI Depok 16424, Indonesia
Search for other works by this author on:
AIP Conf. Proc. 2062, 020061 (2019)
Citation
Zulfa Fuadi, Ardiyansyah Yatim, Rachmah Rizky, Nyayu Aisyah, Idrus Alhamid, Budihardjo Budihardjo, Nandy Putra; Chiller performance study with refrigerant R290. AIP Conf. Proc. 25 January 2019; 2062 (1): 020061. https://doi.org/10.1063/1.5086608
Download citation file:
Citing articles via
Related Content
Effects of sub-cooler on cooling performance of air conditioning system with natural refrigerant R290
AIP Conference Proceedings (November 2020)
Experimental study of small wall room air conditioner for R-22 retrofitted with R290 95.5%
AIP Conference Proceedings (January 2019)
Exergy analysis of an HCFC-22 and HC-290 operated air conditioning system
AIP Conference Proceedings (June 2017)
Experimental study of performance AC split retrofitting R32 to R290
AIP Conference Proceedings (May 2023)
Domestic ejector air-conditioning system performance using different ejector and refrigerant type
AIP Conference Proceedings (July 2023)