An experimental investigation of the influences ammonia concentration variation to the performances of pump less ammonia-aqua absorption refrigeration system with water flooding evaporator is described. The heat generated in generator and refrigerating effect in evaporator, cooling capacity, coefficients of performance (COP) are investigated. The objective of this study is to investigate the characteristic and influences of the ammonia concentration variation to the performance of pump less absorption refrigeration system with water flooding evaporator as a refrigeration load.. In this research, the generator temperature has been setting constant in 80°C using electric heater, the ammonia concentration in 500 ml solution would be varied in 18%, 27%, 37%, 47%, and 59%. It is concluded that heat generated in generator and refrigerating effect in evaporator decrease with increasing ammonia concentration, while the cooling capacity and COP would increase with increasing ammonia concentration. As a result, it is found that increasing the ammonia concentration would effect on increasing of cooling capacity and COP. The highest the ammonia concentration, the highest cooling capacity and COP would be resulted. The highest cooling capacity and COP resulted respectively are 0.7180 kW and 0.829 at 59% ammonia concentration.
Skip Nav Destination
Article navigation
25 January 2019
THE 10TH INTERNATIONAL MEETING OF ADVANCES IN THERMOFLUIDS (IMAT 2018): Smart City: Advances in Thermofluid Technology in Tropical Urban Development
16–17 November 2018
Bali, Indonesia
Research Article|
January 25 2019
The investigation of influence ammonia concentration variations to the performance of a pump less ammonia-water absorption refrigeration system with water flooding evaporator
Hendra Wijaksana;
Hendra Wijaksana
a)
1)
Doctoral Study Program in Engineering Science, Udayana University Kampus Jendral Sudriran Denpasar
, Bali-Indonesia
Search for other works by this author on:
I. N. S. Winaya;
I. N. S. Winaya
a)
2)
Mechanical Engineering Department, Engineering Faculty, Udayana University Kampus Bukit Jimbaran
, Denpasar, Bali-Indonesia
Search for other works by this author on:
Made Sucipta;
Made Sucipta
2)
Mechanical Engineering Department, Engineering Faculty, Udayana University Kampus Bukit Jimbaran
, Denpasar, Bali-Indonesia
Search for other works by this author on:
Ainul. Ghurri
Ainul. Ghurri
2)
Mechanical Engineering Department, Engineering Faculty, Udayana University Kampus Bukit Jimbaran
, Denpasar, Bali-Indonesia
Search for other works by this author on:
AIP Conf. Proc. 2062, 020053 (2019)
Citation
Hendra Wijaksana, I. N. S. Winaya, Made Sucipta, Ainul. Ghurri; The investigation of influence ammonia concentration variations to the performance of a pump less ammonia-water absorption refrigeration system with water flooding evaporator. AIP Conf. Proc. 25 January 2019; 2062 (1): 020053. https://doi.org/10.1063/1.5086600
Download citation file:
574
Views
Citing articles via
Related Content
Effect of ammonia on atmospheric pre-nucleation clusters containing the common atmospheric ion HSO4- and highly oxidized organic species containing nitrogen
AIP Conference Proceedings (November 2020)
Effective design and development of selective catalytic reactor towards cost and NOx reduction
AIP Conference Proceedings (January 2023)
Study on interfacial bonding properties of aramid fiber composites based on chemical analysis
AIP Conference Proceedings (March 2022)
Study on ammonia gas sensing property of hydrothermally synthesized pure ZnO nanorods
AIP Conference Proceedings (June 2017)
The investigation on the variation of rotten degree in a corn-stalk composting process applied with Jaosu
AIP Conference Proceedings (April 2021)